- Contact Person : Mr. Guang Fuhui
- Company Name : Beijing GFUVE Electronics Co., Ltd.
- Tel : 86-10-85782698
- Fax : 86-10-85781298
- Address : Beijing,Beijing,01117-8 Fortune Street No.67 Chaoyang Road, Chaoyang District, Beijing, China.
- Country/Region : China
- Zip : 100024
GF112B Single-Phase kWh Meter Calibrator
Product Description
It is suitable to test various types single phase meters on site and can also be used to test alternating current parameters.
Features and Functions
Current clamp and meter combined together, colorful and touch-screen display;
One AAA Li-battery can continuously working 4 hours;
Wide voltage, current measurement range, voltage range: 15-300V, current range: 0.05-100A;
Display all the measuring parameters in one screen;
Current clamp has automatic conpensation function, 0.2% class accuracy;
Current clamp has automatic calibration function;
Integration design of the meter and clamp;
16bit high accuracy AD switch 32 bit ARM processor core.
Automatically record and save 999 groups calibrate data;
Micro-multifunction optic sampler
Manual/automatic test inductive single phase meters;Manual/automatic test electric single phase meters;Measure virtual value of alternating voltage (15~300Vrms);Measure virtual value of alternating current (50mA~100Arms);Test parameters: active power, phase angle of voltage and current, frequency and etc.Automatic store testing data, and 999 group test results can be save
Specification
(1) Measure Scope
Voltage: 15—300V(r.m.s)
Current: 5mA—100A(r.m.s)
Phase angle: 0—359.99º
Frequency: 45-65Hz
(2) Accuracy of measurement
Voltage & current: better than 0.2%
Phase angle: better than 0.05º
Frequency: better than 0.005 Hz
Active power: better than 0.5%
Active power energy: better than 0.5%
(3)Working Environment
Temperature: -10°C—+55°C/5%-85%RHD
Humidity: -25°C-+70°C/5%-95% RHD
(4) Dimension
215mm×60mm×30mm
Aperture of current clamp: 20mm/Ø16mm
(5) Weight
Mains:0.25kg
Appendix and bag: 0.3kg
(6) Batteries
AAA type, Li rechargable battery, 750mAh, 3.6V. and it can continuously work 4 hours.
GF112B Single-Phase kWh Meter Calibrator